Canadian flag Proudly Canadian

Free CEC 2024 Voltage Drop & SCCR Calculator

AMPLIFY VOLT — Calculate voltage drop, short-circuit current, ampacity & conduit sizing per Canadian Electrical Code CSA C22.1:2024. Free for electricians and engineers.

Auto Cable & Conduit Sizing

Minimum cable auto-selected for ampacity + VD budget. Conduit sized by CEC fill calculations.

🔗

Multi-Segment VD Analysis

Define nodes in the Node Manager, then pick any route in the Calculator tab.

🛡

Full CEC Code Checks

VD, ampacity, SCCR (Bussmann P2P), bonding (Rule 10-616), GEC (Rule 10-114) all auto-calculated.

⚠️
Information Purposes Only — Verify All Calculations
This calculator is provided as an engineering reference tool for information purposes only. Results are not a sealed engineering document and shall not be relied upon for permit submission, tendering, construction, or any other regulated purpose without independent verification. All calculations must be reviewed, verified, and sealed by a licensed Professional Engineer (P.Eng.) or Master Electrician authorized to practice in the project jurisdiction. Neither the author, I&R Associates, nor Amplify Design Consulting accepts any liability for errors, omissions, misuse, or consequences arising from use of this tool. Use at your own risk.
🔵
Node Manager
Define all nodes (transformer, panels, disconnects). Configure system settings below, then go to Segment Analysis to wire them up.
💡 Tip: Click a node name to rename it. The + button instantly adds a segment in the Segment Analysis tab. The first node (⚡ Source) is the transformer.
⚡ System Configuration
Phase · Voltage · VD Limits · Cable Rules · Transformer — applies to all segments
≥60A feeder → AL  |  <60A / small size → CU
Auto: optimizer picks cable & sets  |  Manual: you pick, calcs still validate
🎯 VD Design Targets
Flat: your design target applies equally to all feeder/panel/meter-stack nodes. Recommended for most projects.
Warn threshold  |  CEC max 3.0%
Hard fail — CEC Rule 8-102
Load endpoints — CEC max 5.0%
🔧 Practical Cable Limits — Auto-Solve Parallel Logic
⚡ Auto-solve will prefer parallel sets over exceeding these per-set limits.  e.g. 400A in raceway → 2×350 MCM AL instead of 1×1000 MCM AL.
Indoor pulls, tight bends
Duct bank pulling
Pulling machines available
No bending constraints
CEC Table 36 AAC sizes
🏭 Source Configuration (for SCCR)
Utility transformer — ISC from kVA and Z% impedance
⚡ Utility Transformer
Short Circuit Calculation (Bussmann P2P Method)
f factor → M factor → ISC at each node — CEC Rule 14-012
OFF ON
One-Line Diagram Preview
Segment Analysis
Cable & conduit auto-sized. ISC/VD calculated per segment.
📊 Results & Reports
VD · SCCR · Ampacity · Bonding · GEC · Feeder Notes
Feeder VD — Rule 8-102
0.00%
Limit 3%
Total VD (Source → Load) — Rule 8-102
0.00%
Limit 5%
📉
Voltage Drop Results
CEC Rule 8-102 — 3% feeder / 5% total
#SegmentFrom → ToLength (ft)Conductor SetsCurrent/SetK (CEC)Area mm²CMSeg VD (V)Seg VD% Cum VD%End VoltageStatus
Formula — CEC Table D5 Circular Mil Method (CSA C22.1 Appendix D)VD = (K × P × L × I) / CM  |  K = CEC resistivity constant (60°C: Cu=11.7 Al=19.6 | 75°C: Cu=12.3 Al=20.6 | 90°C: Cu=12.8 Al=21.6)  |  P = 2 (1φ) or 1.732 (3φ)  |  L = one-way length (ft)  |  CM = Table D5 area (mm²) × 1973.5
Fault Current (SCCR)
Bussmann P2P Method — CEC Rule 14-012
#SegmentLengthC-ValueSets ISC In (A)f FactorM FactorISC Out (A) AIC RatingAIC Status
Bussmann P2Pf = (1.732 × L × ISC_in) / (C × n × V)  |  M = 1/(1+f)  |  ISC_out = ISC_in × M
🔌
Cable Selection Validation (CEC Tables 2/4/D11A/D11B)
Derated ampacity ≥ load current per set
#SegmentConductorTable Base (A)DeratingDerated (A) Load (A)Status
Underground (D11A/D11B): 90°C base ×0.886 for 75°C terminations. Raceway/Free Air: Table 5A ambient derating applied.
🔗
Bonding & Grounding Conductor Requirements
CEC Table 16 / Rule 10-616 and Rule 10-114
⚡ Bonding Conductor Sizing (CEC Table 16 / Rule 10-616)
#SegmentCircuit Ampacity Cu BondingAl BondingCEC Rule
🏠 Grounding Electrode Conductor (CEC Rule 10-114)
Per CEC Rule 10-114(1): Minimum #6 AWG copper or #4 AWG aluminum for services up to 200A.
CEC Rule 8-102 Compliance — Node Status
Cumulative VD from Transformer to each node. Feeder 3% vs Branch/Load 5%
NodeTypeCumulative VD%Targets ▶Design ⚠Warn ✗FailStatusRule
📋
Feeder Notes for Drawings
Auto-generated — copy directly into drawing callouts
Toggle note content ↑
Format: [Amps] [Sets]-[Size] [Material] C/W [Ground] [Material] GRND IN [Conduit] OR EQUAL  [VD%]
⚠️
Engineering Reference Only. Verify with a Professional Engineer or Master Electrician. CEC CSA C22.1:2024. Bussmann P2P per Eaton Bussmann Short-Circuit Guide.  |  amplifydesign.ca
🏠 Suite Feeder Schedule Generator
Auto-generates voltage-drop-limited cable schedule for multi-unit residential suite feeders. Standalone tool — no project setup required.
🏠 Suite Feeder Schedule Generator Auto-calculates max feeder length per conductor size at your demand current
CEC Classification: Meter Stack → Suite Panel = FEEDER (CEC Rule 8-102 — 3% max cumulative). Suite Panel → Outlets = BRANCH (remaining budget to 5% total). VD budget split: feeder consumes budget from source, branch gets whatever remains.
Upstream (MS feeder) VD: %  ·  Branch remaining: 3%
(5% CEC 8-102 total = upstream + feeder + branch)
⚡ Feeder Breaker (for drawing note)
This value appears on the drawing note only. The schedule math is based on the design current (panel × demand factor), not the breaker size. Cable lug fit to be verified against the specified meter stack supplier.
(Optional) Flags cables that MAY exceed typical panelboard plug-on breaker lug ranges. Meter stack breakers often have looser lug ranges — verify with supplier.
Design Current
67A
VD calculated on this
Max VD Allowed
4.16V
2% × 208V
Feeder Breaker
70A
Next standard above demand

Canadian flag About AMPLIFY VOLT — A Proudly Canadian Electrical Code Calculator

AMPLIFY VOLT is a free voltage drop and short-circuit current calculator built for the Canadian Electrical Code (CEC) CSA C22.1:2024. It is designed for electricians, electrical engineers, electrical designers, and contractors working on residential, commercial, and institutional projects across Canada. The tool covers voltage drop calculation using CEC Table D5, SCCR analysis using the Bussmann Point-to-Point (P2P) method, ampacity lookup from CEC Tables 2 and 4, conduit fill sizing per CEC Table 8, bonding conductor sizing per Rule 10-616, and grounding electrode conductor (GEC) sizing per Rule 10-114.

The Suite Feeder Schedule Generator automatically calculates maximum wiring lengths for each conductor size at a given design current, voltage, and voltage drop budget. It produces copy-paste drawing notes formatted for multi-unit residential projects — matching the standard Alberta drafting convention used by electrical engineering firms. Copper and aluminum options are paired at +2 AWG (e.g., #4 CU with #2 AL) based on the resistivity ratio between the two materials.

This calculator was designed by Ibrar, P.Eng. (APEGA), and is published by I&R Associates, an electrical engineering consultancy based in Calgary, Alberta. It is offered free of charge as a contribution to the Canadian electrical trade community. No signup, no ads, no tracking. All results must be verified by a licensed Professional Engineer before use in permit submissions or construction.